Final | 12/29/2015 | 12/30/2015 | 12/30/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Final | 12/23/2015 | 12/23/2015 | 12/23/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3(B)- Dimmer in up bonus room shall have type of lamp suitable for this dimmer as per manufacturers instructions. 210.8- All garage 120 volt receptacles shall have GFCI protection. Garage GFI near panel not working. 300.15- All NM cables shall terminate in a box. 6-3 on back patio. 50 amp breaker turned on at time of inspection. 314.25- All boxes shall have covers or luminaire installed.
|
Rough-In Permanent Service | 11/6/2015 | 11/9/2015 | 11/9/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn receptacle needed in dinning room rough-in p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/5/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/5/2015 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|