Final | 12/5/2016 | 12/6/2016 | 12/6/2016 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton building final ok
|
Electrical Rough-In | 11/11/2016 | 11/14/2016 | 11/14/2016 | A | PASS |
Mark Moncarr
|
|
|
Rooms 31-44 Phone #: ###-#### Inspection requested via web by Kerri Hamilton rough ok cover
|
Electrical Rough-In | 10/31/2016 | 11/2/2016 | 11/2/2016 | A | CANC |
Mark Moncarr
|
|
|
Partial Final Rooms 45-50 Phone #: ###-#### Inspection requested via web by Kerri Hamilton
|
Final | 11/2/2016 | 11/2/2016 | 11/2/2016 | P | PART |
Mark Moncarr
|
|
|
Partial Final Rooms 45-50 Phone #: ###-#### Inspection requested via web by Kerri Hamilton partial final ok
|
Change Status to I | | | 10/31/2016 | | DONE |
Rita DeYoung
|
|
|
permit was finaed in error only partial
|
Final | 10/21/2016 | 10/24/2016 | 10/24/2016 | A | PASS |
Mark Moncarr
|
|
|
Final Inspections for rooms 21 through 30 Phone #: ###-#### Inspection requested via web by Kerri Hamilton on last final I had contactor change out all dishwasher pigtails so they were no longer than 4'. fianl ok
|
Electrical Rough-In | 9/22/2016 | 9/23/2016 | 9/23/2016 | A | PASS |
Mark Moncarr
|
|
|
RMS 45-50 Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok cover rooms stated in notes
|
Electrical Rough-In | 9/14/2016 | 9/15/2016 | 9/15/2016 | A | PASS |
Mark Moncarr
|
|
|
Rooms 21-30 Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok to cover
|
Electrical Rough-In | 9/1/2016 | 9/1/2016 | 9/1/2016 | P | PART |
Mark Moncarr
|
|
|
Rooms 11-20 re-inspect Phone #: ###-#### Inspection requested via web by Kerri Hamilton partial final on rooms 11-20
|
Electrical Rough-In | 8/31/2016 | 8/31/2016 | 8/31/2016 | P | FAIL |
Mark Moncarr
|
|
|
Rooms 11-20 Phone #: ###-#### Inspection requested via web by Kerri Hamilton replace all DW pigtails with max 4' in length, outlet for hood in unit 19 needs re-attached to box, all 2p 20 breakers need changed to 2p 15 max fuse is 15,
|
Electrical Rough-In | 8/15/2016 | 8/16/2016 | 8/16/2016 | P | PASS |
James Ady
|
|
|
Units 11-18 Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rooms 11-20 rough in ok to cover
|
Electrical Rough-In | 7/27/2016 | 7/27/2016 | 7/27/2016 | P | PART |
James Ady
|
|
|
Partial Final Rooms 1-10 Building 2 Please call 30 minutes prior for access Phone #: ###-#### Inspection requested via web by Kerri Hamilton Patial final rooms 1-10 ok
|
Electrical Rough-In | 6/20/2016 | 6/20/2016 | 6/20/2016 | P | PASS |
James Ady
|
|
|
Please call 30 minutes prior so Dan can meet you there. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough in ok Rooms 1 - 10 only
|
Final | 6/6/2016 | 6/6/2016 | 6/6/2016 | P | PART |
James Ady
|
|
|
Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rooms 108-111 208-211 308-311 Final ok
|
Electrical Rough-In | 5/4/2016 | 5/5/2016 | 5/5/2016 | A | PASS |
Eric Story
|
|
|
Please call 30 min prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 108,109,110,111,208,209,210,211,308,309,310,311 ok cover
|
Electrical Rough-In | 4/15/2016 | 4/18/2016 | 4/18/2016 | A | CANC |
Eric Story
|
|
|
Please call Dan 30 min in advance so he can meet there. Rooms: 107,112,113,205,206,207,212,305,306,312,313 Phone #: ###-#### Inspection requested via web by Kerri Hamilton needed final
|
Final | 4/18/2016 | 4/18/2016 | 4/18/2016 | P | PART |
Eric Story
|
|
|
Please call Dan 30 min in advance so he can meet there. Rooms: 107,112,113,205,206,207,212,305,306,312,313 Phone #: ###-#### Inspection requested via web by Kerri Hamilton corrections fixed for units 107,112,113,205,206,207,212,305,306,312,313 ok to occupy
|
Final | 4/14/2016 | 4/15/2016 | 4/15/2016 | A | FAIL |
Daryl DeGrange
|
|
|
Dan Hommel Partial Final Rooms: 106,107,112,143,203,204,205,214,215,303,304,305,314,315 Phone #: ###-#### Inspection requested via web by Kerri Hamilton 106 Rm # not posted No lockout on water heater, Panel directory missed labeled. 107 Rm # not posted, panel directory missed labeled. 112 Rm # not posted, directory miss labeled. 113 RM # not posted, directory miss labeled. 205 Rm #, no directory, wall plate missing. 206 RM # not posted, directory miss labeled. 207 RM #, directory, no water heater lockout. 212 Rm #, directory, Kitchen counter GFCI will not reset. 213 Rm #,directory miss labeled. 305 Rm #, no panel directory, missing wall plate. 306 Rm # not posted,directory missing labeled. 312 Rm#, not posted, directory miss labeled. 313 Rm #,directory miss labeled, counter outlet spacing.
|
Electrical Rough-In | 3/7/2016 | 3/7/2016 | 3/7/2016 | P | PASS |
Eric Story
|
|
|
Rough-in rooms #106, 107, 112, 113, 205, 206, 207, 212, 213, 305, 306, 307, 312, 313. Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 106,107,112,113,205,206,207,206,212,213,305,307,312,313,306 ok cover
|
Final | 2/19/2016 | 2/22/2016 | 2/22/2016 | A | PART |
Eric Story
|
|
|
Partial Final for rooms 303,304,315,316,203,204,215,216,103,104,115,116 Phone #: ###-#### Inspection requested via web by Kerri Hamilton rooms 303,304,315,316,203,204,215,216,103,104,115,116 ok to occupy
|
Final | 2/10/2016 | 2/11/2016 | 2/11/2016 | P | PART |
Eric Story
|
|
|
Room 102 Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton room 102 ok to occupy
|
Electrical Rough-In | 1/21/2016 | 1/21/2016 | 1/21/2016 | P | CANC |
Eric Story
|
|
|
Rough in for (4) first floor units. #''s 103, 104, 114, 115 Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 103,104,114,115 ok cover
|
Final | 1/15/2016 | 1/15/2016 | 1/15/2016 | P | PART |
Eric Story
|
|
|
Partial Final for 1st Floor Units Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 101,116,117 partial ok to occupy
|
Electrical Rough-In | 1/15/2016 | 1/15/2016 | 1/15/2016 | P | PASS |
Eric Story
|
|
|
Rough in for 2nd Floor Units Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 203,204,214,215 ok cover
|
Final | 1/13/2016 | 1/14/2016 | 1/14/2016 | P | PART |
Eric Story
|
|
|
Request for Final on (12) remodeled units. Dan is the contact Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 201,202,216,217,301,302,316,317. Partial final to occupy ok
|
Electrical Rough-In | 1/14/2016 | 1/14/2016 | 1/14/2016 | P | PASS |
Eric Story
|
|
|
Rough in for 3rd floor units. Dan is the site contact Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 303,304,315,314 ok cover
|
Electrical Rough-In | 11/30/2015 | 12/1/2015 | 12/1/2015 | A | PASS |
Eric Story
|
|
|
DAN HOMMEL Phone #: ###-#### Inspection requested via web by Kerri Hamilton rooms 101/117/116/102 ok cover
|
Electrical Rough-In | 11/24/2015 | 11/25/2015 | 11/25/2015 | A | PASS |
Eric Story
|
|
|
DJ Pickett Phone #: ###-#### Inspection requested via web by Kerri Hamilton rooms 201/202/216/217 ok cover
|
Electrical Rough-In | 11/19/2015 | 11/20/2015 | 11/20/2015 | A | PASS |
Eric Story
|
|
|
DJ Pickett Phone #: ###-#### Inspection requested via web by Kerri Hamilton 3rd floor romms 301/302/316/317 rough-in ok cover
|
Conference | 11/17/2015 | 11/17/2015 | 11/17/2015 | P | DONE |
Eric Story
|
|
|
Please call Brad Hoots at ###-#### 30 minutes prior so he can meet you there. Phone #: ###-#### Inspection requested via web by Kerri Hamilton discussed kitchen remodel only. recepacle layouts and notching cinder block
|
Issue PAID IN FULL permit | | | 11/17/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/17/2015 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|
First Notice | 12/6/2016 | 12/6/2016 | | | |
Mark Moncarr
|
|
|
|
First Notice | 10/24/2016 | 10/24/2016 | | | |
Mark Moncarr
|
|
|
|