Final | 4/25/2016 | 4/26/2016 | 4/26/2016 | A | PASS |
Rock A. Hudson
|
|
|
Please call Todd Sellman prior to inspection Phone #: ###-#### Inspection requested via web by Todd Sellman Final ok
|
Final | 12/8/2015 | 12/9/2015 | 12/9/2015 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Sellman as per manufacturer- 50 amp maximum on top position of all in one. Relocate 80 amp breaker and turn on 200 amp main. 250 .94- intersystem bus bar required
|
Rough-In Permanent Service | 12/7/2015 | 12/8/2015 | 12/8/2015 | A | PASS |
Rock A. Hudson
|
|
|
Tim Phone #: ###-#### Service change ready at time of inspection. #2 SER shall be fused down to 80 amp as per 310.15(B)(7). p/s o/h rec ok
|
Issue PAID IN FULL permit | | | 11/19/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/19/2015 | | DONE |
|
|
|
This permit was created on the web by Todd Sellman
|