First Notice | 1/8/2016 | 1/8/2016 | 8/8/2016 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Celinda Winters
|
Final | 1/7/2016 | 1/8/2016 | 1/8/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters All GFCI devices located in panel. Final ok
|
Final | 12/17/2015 | 12/17/2015 | 12/17/2015 | P | FAIL |
Rex Boyles
|
|
|
El Habenero Taco Truck Phone #: ###-#### Inspection requested via web by Celinda Winters 210.8(B)(2)-All 15 and 20 amp receptacles in other than dwelling kitchens shall have GFCI protection
|
Final | 11/25/2015 | 11/27/2015 | 11/27/2015 | A | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters correction done, not ready for final at this time. Power not connected
|
Permanent Service | 11/27/2015 | 11/27/2015 | 11/27/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters p/s o/h n ok
|
Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 | P | FAIL |
Rock A. Hudson
|
|
|
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters 110.24- Available fault current shall be posted with date calculated prior to permenant service inspection. 358.22- Conductor fill shall ot exceed that permitted by the percentage specified in table 1 chapter 9. .122" max .185" installed. 3/4" EMT conduit minimum. 60% fill applies due to 16" length. Conduit ok
|
Final | 11/23/2015 | 11/23/2015 | 11/23/2015 | A | CANC |
Rock A. Hudson
|
|
|
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters Needed permenant service inspection.
|
Issue PAID IN FULL permit | | | 11/23/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 11/23/2015 | | |
|
|
|
|
Application received | | | 11/23/2015 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|