Final | 4/24/2016 | 4/25/2016 | 4/25/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|
Final | 4/14/2016 | 4/15/2016 | 4/15/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 110.3- Devices shall be wired as to manufacturers instructions. Up hall open neutral. 110.3- Out GFCI and out receptacles not working. 300.4(G)- Connector with #4 or larger conductors shall have a bushing installed. Meter main. 406.5- Garage receptacle shall be secured to box.
|
Rough-In Permanent Service | 11/25/2015 | 11/25/2015 | 11/25/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Rough in ok cover p/s o/h n ok
|
Issue PAID IN FULL permit | | | 11/25/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/24/2015 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|