First Notice | 4/14/2016 | 4/14/2016 | 7/6/2016 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Stan Woodward
|
Final | 4/14/2016 | 4/14/2016 | 4/14/2016 | P | PASS |
Rex Boyles
|
|
|
Seal coduits Phone #: ###-#### Inspection requested via web by Stan Woodward seal offs done and lockoffs on vacuums installed final ok
|
Final | 4/13/2016 | 4/13/2016 | 4/13/2016 | P | PART |
Rex Boyles
|
|
|
Final Phone #: ###-#### Inspection requested via web by Stan Woodward partial final-everything finaled except seal offs for pumps temp. occupancy ok
|
Electrical Rough-In | 3/29/2016 | 3/30/2016 | 3/30/2016 | A | PASS |
Rex Boyles
|
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by Stan Woodward r/i t grid ceilings ok
|
Rough-In Permanent Service | 2/26/2016 | 2/26/2016 | 2/26/2016 | P | PASS |
Rex Boyles
|
|
|
Underground Phone #: ###-#### Inspection requested via web by Stan Woodward remainder of exterior underground raceways r/i ok 100% NOTE:NO P/S NEEDED ALREADY RECEIVED YESTERDAY
|
Rough-In Permanent Service | 2/25/2016 | 2/25/2016 | 2/25/2016 | P | PASS |
Rex Boyles
|
|
|
Underground to tanks and service have the Arc fault labels installed Phone #: ###-#### Inspection requested via web by Stan Woodward r/i u.ground raceways from new bldg. out to fuel storage tanks and from existing pumps out to vault and from vault back to new bldg. ok 2" from new bldg. out to vaccums also ok to cover. p/s u/g n ok
|
Permanent Service | 2/18/2016 | 2/18/2016 | 2/18/2016 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Stan Woodward need available fault current 110.24(A)- service equipment in other than dwelling units shall be legibly marked in the field with the maximum available fault current including date and calculation.
|
Electrical Rough-In | 2/10/2016 | 2/10/2016 | 2/10/2016 | P | PASS |
Rex Boyles
|
|
|
Cover for the walls Phone #: ###-#### Inspection requested via web by Stan Woodward r/i all walls and bath ceilings ok
|
Electrical Rough-In | 1/15/2016 | 1/15/2016 | 1/15/2016 | P | PASS |
Rex Boyles
|
|
|
I would like to get a cover on the underground for the Car Wash at the Jacksons new Store on Broadway Phone #: ###-#### Inspection requested via web by Stan Woodward r/i underslab conduits in car wash ok
|
Electrical Rough-In | 1/7/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Rex Boyles
|
|
|
We would like an inspection for cover on our underground, we will need to uncover the slab site first thing in the morning, If possible could you come by after 10 in the morning to make sure its uncovered for you. Phone #: ###-#### Inspection requested via web by Stan Woodward r/i underslab raceways and floorboxes ok to cover
|
Electrical Rough-In | 12/4/2015 | 12/4/2015 | 12/4/2015 | P | PASS |
Rex Boyles
|
|
|
Underground from temporary pole to store Phone #: ###-#### Inspection requested via web by Stan Woodward r/i t/ s conduit ok to cover
|
Conference | 12/2/2015 | 12/2/2015 | 12/2/2015 | P | DONE |
Rex Boyles
|
|
|
Temporary underground to existing store and temp power Phone #: ###-#### Inspection requested via web by Stan Woodward discuss picking up existing conduit to re feed store with 200 amp temp. service. OK to use existing bldg. grounding electrode instead of equipt. grounding conductor with feeders for temp. power.
|
Issue PAID IN FULL permit | | | 11/30/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/30/2015 | | DONE |
|
|
|
This permit was created on the web by Stan Woodward
|