Final | 5/16/2016 | 5/17/2016 | 5/17/2016 | A | PASS |
Eric Story
|
|
|
Ryan Barnes Please call 30 minutes in advance for access Phone #: ###-#### Inspection requested via web by Kerri Hamilton All canning areas where equipment has not been set will need seperate permit. final for this permit ok cover
|
Final | 5/6/2016 | 5/9/2016 | 5/9/2016 | A | PART |
Eric Story
|
|
|
We spoke with Rex and informed him that this needs to be a later AM inspection and he obliged. Thank you! Phone #: ###-#### Inspection requested via web by Kerri Hamilton all office areas and tasting bar ok to occupy, will still need to verify equipmment when is wired to innsure it is free of shorts and competed.
|
Permanent Service | 5/2/2016 | 5/3/2016 | 5/3/2016 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton p/s u/g n ok 120/240 volt 1 phase parking lot lighting service on northwest corner of bldg. ALSO:"partial final" rooftop final ok
|
Electrical Rough-In | 4/25/2016 | 4/26/2016 | 4/26/2016 | A | CANC |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton wrong permit called in
|
Electrical Rough-In | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | CANC |
Eric Story
|
|
|
Temp Occ and partial Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton needed partial final
|
Final | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | PART |
Eric Story
|
|
|
Temp Occ and partial Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton office areas walls ok to move furniture in tasting bar area and walk-in cooler ok for partial final
|
Electrical Rough-In | 4/21/2016 | 4/22/2016 | 4/22/2016 | A | FAIL |
Eric Story
|
|
|
Temp Occ in Office and Occ in Tasting Room Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton 210.8 (b)(5) receptacles located within 6' of a sink shall have GFCI protection 4-s are not rated in a damp location 422.51 vending machines manufactored after 2005 shall have a GFCI protected cord from manufacter cant not verify they are not on site
|
Conference | 4/20/2016 | 4/20/2016 | 4/20/2016 | P | DONE |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton discussed low volt wiring and items for temp oc
|
Conference | 3/23/2016 | 3/24/2016 | 3/24/2016 | A | DONE |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discussed lockout for pumps and locations of disconnects
|
Electrical Rough-In | 3/24/2016 | 3/24/2016 | 3/24/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton bar area walls ok cover
|
Permanent Service | 3/9/2016 | 3/9/2016 | 3/9/2016 | P | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1200 amp p/s u/g n ok
|
Permanent Service | 3/7/2016 | 3/8/2016 | 3/8/2016 | P | FAIL |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton 230.95 (c) ground fault protection required pryor to being energized
|
Electrical Rough-In | 2/19/2016 | 2/22/2016 | 2/22/2016 | P | PASS |
Bob Reichert
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok cover u/g for rv pad west side
|
Electrical Rough-In | 2/17/2016 | 2/18/2016 | 2/18/2016 | A | PASS |
Rock A. Hudson
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton Island not ready. Tasting room wall rough in ok cover
|
Electrical Rough-In | 2/1/2016 | 2/2/2016 | 2/2/2016 | A | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton boiler and electrical room ok cover
|
Electrical Rough-In | 1/26/2016 | 1/27/2016 | 1/27/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton bathrooms hard lids ok cover
|
Electrical Rough-In | 1/23/2016 | 1/25/2016 | 1/25/2016 | P | PASS |
Eric Story
|
|
|
Underground in tasting room Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground for tasting room ok cover
|
Electrical Rough-In | 1/12/2016 | 1/13/2016 | 1/13/2016 | A | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton walls only ok cover
|
Electrical Rough-In | 12/17/2015 | 12/18/2015 | 12/18/2015 | A | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground as per contractors print ok cover
|
Electrical Rough-In | 12/15/2015 | 12/16/2015 | 12/16/2015 | P | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground as per contrators print ok cover
|
Electrical Rough-In | 12/9/2015 | 12/10/2015 | 12/10/2015 | A | PASS |
Eric Story
|
|
|
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground for relocating panels ok cover
|
Issue PAID IN FULL permit | | | 11/30/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/30/2015 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|
First Notice | 5/17/2016 | 5/17/2016 | | | |
Eric Story
|
|
|
|