Final | 3/22/2016 | 3/23/2016 | 3/23/2016 | A | PASS |
Eric Story
|
|
|
The home owners should be home, the outlet by the fireplace has been changed to a GFI and the light in the bath area has been changed to a "non open lamp" fixture, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren corrections fixed final ok
|
Final | 3/17/2016 | 3/18/2016 | 3/18/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 406.4(D)(2)- Grounding type receptacle outlet installed on an ungrounded circuit. either GFCI protect or change to a 2-wire receptacle. 410.10(D)- All luminaires located with in 3' horizontally and 8' vertical of tub edge or shower threshold shall be damp location rated.
|
Permanent Service | 12/15/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Bob Reichert
|
|
|
We are upgrading the service on this home today, IP will be reconnecting the power this afternoon, I am hoping to get a service insp this afternoon just in case IP needs something approved before reinstalling the meter, please call for any questions, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren p/s o/h rec ok, at final check for 2nd ground rod, rods pounded down, labels, straps,
|
Electrical Rough-In | 12/3/2015 | 12/4/2015 | 12/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting an approval for cover inspection, the service will be done on a later date. The customers are living in the basement, please knock before entering, but if the customer is not home, the lock box code is 2701. Plz call for any questions, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Required receptacles in dining area around fireplace will be surface mount wiremold. Check box above living fireplace framing only 1" deep. Temp wiring to be removed when service change is done to refeed basement which is lived in. Main floor rough in ok cover
|
Issue PAID IN FULL permit | | | 12/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/3/2015 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|