Final | 1/26/2016 | 1/26/2016 | 1/26/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
Permanent Service | 1/6/2016 | 1/6/2016 | 1/6/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender corrections fixed p/s u/g rec ok just need three phase meter for pack
|
Permanent Service | 12/30/2015 | 12/30/2015 | 12/30/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 110.9- Equipment intended to interupt current at fault levels shall have an interupting rating sufficient for fault current available at line terminals. 13,283 available fault current on 10,000 rated main breaker.
|
Permanent Service | 12/28/2015 | 12/28/2015 | 12/28/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender NEC 110.22 Identification of disconnecting means. NEC 110.24 Field marking available fault current.
|
Electrical Rough-In | 12/14/2015 | 12/14/2015 | 12/14/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender walls onyl ok cover, 2nd floor
|
Issue PAID IN FULL permit | | | 12/8/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/8/2015 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|
First Notice | 1/26/2016 | 1/26/2016 | | | |
Rock A. Hudson
|
|
|
|