First Notice | 7/14/2017 | 7/14/2017 | 2/6/2018 | | DONE |
Eric Story
|
|
|
|
Final | 7/13/2017 | 7/14/2017 | 7/14/2017 | A | PASS |
Eric Story
|
|
|
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy Final ok
|
Final | 2/13/2017 | 2/13/2017 | 2/13/2017 | P | NR |
Eric Story
|
|
|
Matt. Phone #: ###-#### Inspection requested via web by Sean DeLacy Elevator room needs to be finished, 4th floor has reversed polarity from elevator on right side of hall room number 407/all panels shall be nand discconects labeled
|
Electrical Rough-In | 8/9/2016 | 8/10/2016 | 8/10/2016 | A | PASS |
Rock A. Hudson
|
|
|
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy Discussed need to 1 side drywall for firewalls between guest rooms. OK for firewalls only, will be called out to check progress. North and south exterior wall myrtle side 2nd floor and all of 4th floor fire lid corridor rough in ok cover
|
Electrical Rough-In | 7/25/2016 | 7/26/2016 | 7/26/2016 | A | NH |
Rock A. Hudson
|
|
|
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy Called, left message, waited 10 minutes, must recall Dave called and informed of a 1'x1' soffit that will be built around each room and that electrical not being ran through soffits until rooms are wired.
|
Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 | A | PASS |
Daryl DeGrange
|
|
|
Dave. Cover inspection on lids for units. Phone #: ###-#### Inspection requested via web by Sean DeLacy Rough-in ok cover 2nd &3rd floors hard lid ceilings
|
Electrical Rough-In | 6/23/2016 | 6/23/2016 | 6/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
Dave. Cover inspection on 2nd floor. Phone #: ###-#### Inspection requested via web by Sean DeLacy Sign off book not ready yet. 2nd floor corridor fire lid rough in ok cover
|
Conference | 5/10/2016 | 5/11/2016 | 5/11/2016 | A | DONE |
Rex Boyles
|
|
|
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy discuss installation of mc cable supported by listed caddy hangers with 7 cables in each is OK to do. Also issue with fire pump room with other systems in same room, 2hr ceiling being installed to eliminate problem also OK
|
Conference | 2/19/2016 | 2/22/2016 | 2/22/2016 | A | DONE |
Rex Boyles
|
|
|
Dave Johnson is on site Phone #: ###-#### Inspection requested via web by Buster Bowen discuss fire pump requirementa and fire pump room requirements. Dave agrees to move upright switchgear section for fire pump from main electric room into "fire pump" room. Also they will move loadcenters, irrigation controller and generator transfer switch shown in fire pump room out of fire pump room. All other equipment associated with fire pump and domestic water, controls, etc. ok in fire pump room. No generator emergency back up power required for fire pump if utilities come in underground. NFPA20-4.12.1.1.4-rooms containing fire pumps shall be free from storage, equipment, and pentrations not essential to the operation of the pump and related components.
|
Conference | 2/17/2016 | 2/17/2016 | 2/17/2016 | P | DONE |
Rex Boyles
|
|
|
Dave. Fire Pump service conference. Phone #: ###-#### Inspection requested via web by Sean DeLacy Asked Dave to run separate raceway from utility transformer straight to fire pump controller. Also there are issues with fire pump room / mechanical room and no generator back up for fire pump. Group conference needed with appropriate people prior to continuing work in this part of project.
|
Electrical Rough-In | 2/9/2016 | 2/9/2016 | 2/9/2016 | P | PASS |
Rex Boyles
|
|
|
Uffer inspections. Dave Johnson is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen r/i ok
|
Electrical Rough-In | 2/2/2016 | 2/2/2016 | 2/2/2016 | P | PASS |
Rex Boyles
|
|
|
Dave. Underground. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i u.ground from termination cab. over to stub up area ok
|
Issue PAID IN FULL permit | | | 12/8/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/8/2015 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|