Permit Information
Permit NumberELE15-03958
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 21 N ALLUMBAUGH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Demo of existing electrical equipment. Install of new lighting, power, gear, and fire alarm.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice4/12/20164/12/201611/14/2018 DONE
DetailsRock A. Hudson
This permit finaled on the web by Tom Jenkins
Print Statement  9/26/2016 DONE
Final4/12/20164/12/20164/12/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Final ok
Final4/11/20164/12/20164/12/2016AFAIL
DetailsRock A. Hudson
Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins
110.16- Arc flash stickers on new disconnecting means.
210.64- A receptacle outlet shall be located within 50' of new service.
210.70- Rooms containing electrical equipment shall have luminaire installed.
300.15- In ele rm conductors hanging out of conduit shall terminate in a box.
330.30- Mezz. MC shall be secured within 12" of box. SL at switch.
422.51- Vending machine shall have GFCI protection.
Electrical Rough-In3/16/20163/17/20163/17/2016APASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Thomas Jenkins rough-in ok cover underground to sign
Electrical Rough-In3/16/20163/16/20163/16/2016PFAIL
DetailsRock A. Hudson
Underground for sign. Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Verbal with on site wireman. 300.5- Minimum depth of under roadway 24". 18 to 20 at time of inspection.
Electrical Rough-In3/11/20163/11/20163/11/2016PCANC
DetailsRock A. Hudson
Inspection for underground conduit Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Inspection cancelled from web by: Thomas Jenkins
Electrical Rough-In2/22/20162/23/20162/23/2016APASS
DetailsRock A. Hudson
Need wall and ceiling inspection in the two large gym areas. Please feel free to contact me with any questions. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Gym and storage areas walls and hard lids rough in ok cover
Electrical Rough-In2/4/20162/5/20162/5/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Thomas Jenkins
Bath and locker rooms rough in ok cover
Permanent Service1/25/20161/25/20161/25/2016APASS
DetailsRock A. Hudson
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins p/s o/h rec ok
Electrical Rough-In1/25/20161/25/20161/25/2016PPASS
DetailsRock A. Hudson
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins Walls and hard lids in front offices, locker room not ready, main floor as noted on print. Rough in ok cover
Permanent Service1/21/20161/22/20161/22/2016PFAIL
DetailsRock A. Hudson
We need a service inspection for IPCO to reconnect service. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins
110.22- Each disconnecting means shall be identified as to its purpose.
110.24- Available fault current chall be posted with date calculated prior to permanent service inspection. 250.90- Standard lock nuts and bushings shall not be only means of bonding service enclosures. bonding bushings required at all nipples.
300.4- Replace all bushings that are missing or damaged.
230.71- Max number of disconnecting means shall not exceed 6.
Drawing shows total load of 301 amp plus well at 40 amps on 500 KCMIL service entrance rated at 380 amps 75 degrees.
Issue PAID IN FULL permit  12/9/2015 DONE
Payment received via Govolutions
Application received  12/9/2015 DONE
This permit was created on the web by Thomas Jenkins