First Notice | 12/29/2015 | 12/29/2015 | 2/17/2016 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Lonnie Sorichta
|
Final | 12/28/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rex Boyles
|
|
|
Lock box code 0328 Fix corrections Thank you Phone #: ###-#### Inspection requested via web by Lonnie Sorichta corrections made final ok
|
Final | 12/22/2015 | 12/23/2015 | 12/23/2015 | A | FAIL |
Bob Reichert
|
|
|
Inspect two outlets. (MC was pulled apart, fixed MC, re-fed outlets.) Lock Box Code- 0328 Phone #: ###-#### Inspection requested via web by Lonnie Sorichta called, left correction notice, NEC 408.4 shall finish panel schedule, 330.30 shall secure mc cable within 12" of box, 300.11 shall securely mount box
|
Electrical Rough-In | 12/14/2015 | 12/15/2015 | 12/15/2015 | A | PASS |
Rex Boyles
|
|
|
Suite 100 Lock box code- 0328 Inspection for cover. Fixed MC that was pulled apart./ Re-pulled MC. Thank you Phone #: ###-#### Inspection requested via web by Lonnie Sorichta r/i wall for receptacle relocation ok
|
Issue PAID IN FULL permit | | | 12/14/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Override - Parcel Holds | | | 12/14/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/14/2015 | | DONE |
|
|
|
|
Application received | | | 12/14/2015 | | |
|
|
|
|