Final | 6/2/2016 | 6/2/2016 | 6/2/2016 | P | PASS |
Eric Story
|
|
|
call for access code; Cal Phone #: ###-#### Final ok
|
Override - Parcel Holds | 6/2/2016 | 1/1/1900 | 6/2/2016 | | |
|
|
|
electrical only
|
Rough-In Permanent Service | 2/22/2016 | 2/22/2016 | 2/22/2016 | P | CANC |
Rock A. Hudson
|
|
|
Cal Phone #: ###-####
|
Print Statement | | | 1/6/2016 | | DONE |
|
|
|
|
Rough-In Permanent Service | 12/23/2015 | 12/23/2015 | 12/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Cal Phone #: ###-#### Rough in ok cover p/s u/g n ok Underground to service not connected due to placement will not work.
|
Reinspection Fee (no hold) | 12/23/2015 | 12/23/2015 | 12/23/2015 | A | PASS |
Bob Reichert
|
|
|
see fail inspection 12/23/2015
|
Final | 12/23/2015 | 12/23/2015 | 12/23/2015 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by cal crosby corrections not done, called, fee due, wrong type request
|
Rough-In Permanent Service | 12/22/2015 | 12/22/2015 | 12/22/2015 | P | FAIL |
Rock A. Hudson
|
|
|
rough-in Phone #: ###-#### Inspection requested via web by cal crosby 250.28- Main bonding jumper screw shall be installed. 300.4- NM cable and bell wire shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface. garage outlet, garage door sensor wires. 408.7- Unused breaker spaces shall be closed.
|
Issue PAID IN FULL permit | | | 12/22/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/22/2015 | | DONE |
|
|
|
This permit was created on the web by cal crosby
|