Final | 4/11/2016 | 4/11/2016 | 4/11/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Don Conley All ungrounded circuits with grounded receptacles GFCI protected. Existing hot tub disconnected in panel, reconnecting will be violation due to overhead service entrance clearance and underground too shallow. Final ok
|
Electrical Rough-In | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley Basement and kitchen areas only rewired. All existing receptacles had equipment grounds ran seperate from old NM cable. All grounding taps not good do to whole house replumbed with plastic pipe. Contractor to address grounding type receptacles at future time. Rough in ok cover
|
Permanent Service | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley p/s o/h rec ok
|
Electrical Rough-In | 12/28/2015 | 12/29/2015 | 12/29/2015 | A | FAIL |
Rock A. Hudson
|
|
|
loc box code 3370 Phone #: ###-#### Inspection requested via web by Don Conley 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface, secure NM 1 1/4" from framing surface. Existing and new. 408.7- Unused breaker spaces shal be closed. Verbal with Troy
|
Issue PAID IN FULL permit | | | 12/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/28/2015 | | DONE |
|
|
|
This permit was created on the web by Don Conley
|