Final | 3/7/2016 | 3/7/2016 | 3/7/2016 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt corrections made final ok
|
Final | 3/1/2016 | 3/2/2016 | 3/2/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 210.8- All bathroom receptacle outlets shall have GFCI protection. Stool. 210.52(C)(5) ex- Peninsular counter receptacle outlet shall not be located more than 6" back from edge of over hang. 406.4(D)(2)- Grounded type receptacle outlets installed on ungrounded circuit shall have GFCI protection or be changed to ungrounded type receptacle. 408.4- Circuit directory shall be completed.
|
Electrical Rough-In | 12/30/2015 | 12/30/2015 | 12/30/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt Kitchen and M. bath rough in ok cover
|
Issue PAID IN FULL permit | | | 12/30/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/29/2015 | | DONE |
|
|
|
This permit was created on the web by John VanZandt
|