Permit Information
Permit NumberELE16-00043
StatusFinaled
Name RUMMER ELECTRIC
Site Address 2005 N LIBERTY ST
Project Name 
Customer Number34550
ePlanReviewNo
Description
Complete Installation (includes room count and per: new house
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/24/20164/25/20164/25/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
Final ok
Final4/14/20164/15/20164/15/2016PFAIL
DetailsRock A. Hudson
call if you need the code Phone #: ###-#### Inspection requested via web by Neal Rumsey
210.8- Christmas GFCI shall be located in a readily accessible location. Below 6'7".
210.8(A)(2)- All 15 or 20 amp 120 volt receptacle outlets shall have GFCI protection. Opener outlet.
404.8- Switch used as disconnect for furnace shall be located under 6'7".
Back patio light not working.
Rough-In Permanent Service1/12/20161/13/20161/13/2016PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections fixed rough-in ok cover p/s o/h n ok
Rough-In Permanent Service1/12/20161/12/20161/12/2016PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
210.52(A)(2)1- Walls 2' or wider shall have a receptacle outlet install to serve wall space.
250.134- Metal box in net panel shall be connected to equipment grounding conductor.
300.4- In garage gronding electrode conductor wher ran through bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage by nail plates.
300.4(G)- Raceways or connectors containing #4 or larger conductors shall have a bushing installed to protect wiring.
352.48- All joints between conduit bodies shall be done by an approved method. Garage LB to junction box. Glue BA to LB.
Rough-In Permanent Service1/11/20161/11/20161/11/2016ANR
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Neal Rumsey called electrical contractor, told him BLD description doesn't match street address, no address or job id posted, no esc signs posted, no u/g seen, ground wire cut at liberty service, shall protect nm cable within 6' of attic access, shall move outside boxes forward to be flush with finished surface on outsides of building, shall provide receptacles in 2' wall space, shall protect nm cable with nailplates, shall meet osha safety rules in liberty side with barrier at top of stairs and hall, shall establish grounding electrode for post side of structure, shall provide service riser straps within 3' of panel, add guy kit terminations
Issue PAID IN FULL permit  1/6/2016 DONE
Payment received via Govolutions
Application received  1/6/2016 DONE
This permit was created on the web by Neal Rumsey