Final | 3/10/2016 | 3/11/2016 | 3/11/2016 | A | PASS |
Daryl DeGrange
|
|
|
Code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut correction done, final ok
|
Final | 3/10/2016 | 3/10/2016 | 3/10/2016 | P | FAIL |
Eric Story
|
|
|
Code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut corrections not fixed (receptacle under shelves non GFCI protected and reverse polarity)
|
Final | 3/10/2016 | 3/10/2016 | 3/10/2016 | A | FAIL |
Daryl DeGrange
|
|
|
Door code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut Not all corrections have been completed.
|
Final | 3/8/2016 | 3/9/2016 | 3/9/2016 | A | FAIL |
Rex Boyles
|
|
|
Door code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.8(B)(7)- receptacles within 6 foot of sink shall have GFCI protection (back wall of bar), 110.16-Arc flash warning label on loadcenters, caulk walk in penetrations, old AC cable put in box or cut off.
|
Final | 3/4/2016 | 3/4/2016 | 3/4/2016 | P | CANC |
Rex Boyles
|
|
|
Key code 234 Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Inspection cancelled from web by: Chris Chesnut
|
Electrical Rough-In | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | PASS |
Rex Boyles
|
|
|
234 key box code Phone #: ###-#### Inspection requested via web by Chris Chesnut r/i walls and ceiling ok
|
Conference | 1/18/2016 | 1/19/2016 | 1/19/2016 | A | DONE |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Chesnut discuss mc cable use and ber receptacles requiring GFCI protection , exit and egress lighting and bathroom GFCI protected receptacles.
|
Issue PAID IN FULL permit | | | 1/18/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 1/18/2016 | | |
|
|
|
|
Application received | | | 1/18/2016 | | DONE |
|
|
|
This permit was created on the web by Chris Chesnut
|
First Notice | 3/11/2016 | 3/11/2016 | | | |
Daryl DeGrange
|
|
|
|