Print Statement | | | 6/16/2016 | | DONE |
|
|
|
|
Final | 2/3/2016 | 2/3/2016 | 2/3/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale Unable to comply directly above wall due to 3 hour fire rating and moving would compromise rating, rest of new install ok. Final ok
|
Final | 2/3/2016 | 2/3/2016 | 2/3/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Cyndi Dale 300.4(E)- Cables, Raceways, or Boxes Installed in or Under Roof Decking. A cable, raceway, or box, installed in exposed or concealed locations under metal-corrugated sheet roof decking, shall be installed and supported so there is not less than 38 mm (1 1/2 in.) measured from the lowest surface of the roof decking to the top of the cable, raceway, or box. A cable, raceway, or box shall not be installed in concealed locations in metal-corrugated, sheet decking–type roof. New cables only.
|
Electrical Rough-In | 1/19/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Cyndi Dale North end of building. Demising wall rough in ok cover
|
Issue PAID IN FULL permit | | | 1/19/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 1/19/2016 | | |
|
|
|
|
Application received | | | 1/19/2016 | | DONE |
|
|
|
This permit was created on the web by Cyndi Dale
|