Final | 3/7/2017 | 3/7/2017 | 3/7/2017 | P | PASS |
Tom Saunders
|
|
|
Juanita or Rick Phone #: ###-####-please call when on your way...
ok to final
|
Electrical Rough-In | 12/29/2016 | 12/30/2016 | 12/30/2016 | A | PASS |
Tom Saunders
|
|
|
Juanita Phone #: ###-####...
corrections made...ok to cover
|
Electrical Rough-In | 12/12/2016 | 12/13/2016 | 12/13/2016 | A | FAIL |
Tom Saunders
|
|
|
Juanita Phone #: ###-####....
too much to list...on correction notice
|
Electrical Rough-In | 9/22/2016 | 9/22/2016 | 9/22/2016 | P | CANC |
Tom Saunders
|
|
|
Juanita Phone #: ###-####
wrong type of inspection
|
Rough-In Permanent Service | 9/22/2016 | 9/22/2016 | 9/22/2016 | P | PASS |
Tom Saunders
|
|
|
Juanita Phone #: ###-####
ok to cover wiring to sub panel in garage...rough inspection will need to be scheduled for further work done in garage-wiring in walls or surface mount
p/s u/g n ok
|
Electrical Rough-In | 9/15/2016 | 9/16/2016 | 9/16/2016 | P | FAIL |
Eric Story
|
|
|
Juanita Phone #: ###-####
334.30 romex shall be supported within 12" of box
300.4(b) conductor larger than #4 shall have bushing
all openings shall be closed-sub panel
conference needed
|
Conference | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | DONE |
Rock A. Hudson
|
|
|
Juanita Phone #: ###-#### Discussed owner has been general contractor from California in past. Required dedicated garage receptacle circuit, bathroom circuit, 200 amp service, and state law requires owner and or immediate family to do work.
|
Application received | | | 1/20/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/20/2016 | | DONE |
|
|
|
|