Final | 6/30/2016 | 7/1/2016 | 7/1/2016 | A | PASS |
James Ady
|
|
|
Late morning - Mark Phone #: ###-#### Corrections made. Final ok
|
Final | 6/29/2016 | 6/29/2016 | 6/29/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### 210.52- Receptacle shall be added to right of range within 24" of right edge. 314.25- All covers and lights shall be installed on boxes. 334.12- NM cable shall not be installed where subject to physical damage and where exposed outside. Cover patio lid and wire to disp. protect with conduit and change box to conduit to terminate to.
|
Permanent Service | 6/20/2016 | 6/21/2016 | 6/21/2016 | A | PASS |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### p/s o/h n ok
|
Final | 6/20/2016 | 6/20/2016 | 6/20/2016 | P | CANC |
Rock A. Hudson
|
|
|
Mark-has appoiment from until 3 and would like inspection after if possible Phone #: ###-#### Needed permenant inspection
|
Permanent Service | 6/20/2016 | 6/20/2016 | 6/20/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Mark-has appoiment from until 3 and would like inspection after if possible Phone #: ###-#### 250.28- Main bonding jumper screw shall be installed
|
Electrical Rough-In | 5/24/2016 | 5/24/2016 | 5/24/2016 | P | PASS |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### Will call next week to check make up in boxes. Walls and Ceilings rough in ok cover
|
Conference | 4/21/2016 | 4/21/2016 | 4/21/2016 | P | DONE |
Eric Story
|
|
|
Mark Phone #: ###-#### discussed layout of service and feeders to be used and also layout for overhead feed
|
Electrical Rough-In | 4/12/2016 | 4/13/2016 | 4/13/2016 | A | CANC |
Eric Story
|
|
|
would like call ahead; Mark Phone #: ###-#### needed conference
|
Conference | 4/13/2016 | 4/13/2016 | 4/13/2016 | P | DONE |
Eric Story
|
|
|
would like call ahead; Mark Phone #: ###-#### discussed wiring and code requirements on straw house and mounting of receptacles and panel
|
Application received | | | 1/27/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/27/2016 | | DONE |
|
|
|
|