Permit Information
Permit NumberELE16-00390
StatusFinaled
Name PHE ELECTRIC INC
Site Address 7570 W SAXTON DR
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Electrical Wiring of club house
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/25/20171/25/20171/25/2017PPASS
DetailsMark Moncarr
Christina Phone #: ###-#### Talked with Doug. Powerhouse is going to pull new permit for 2 light poles and signs so they can final out clubhouse and so they can get a C of O
Electrical Rough-In8/18/20168/18/20168/18/2016PPASS
DetailsJames Ady
(2) Pole lights and entry signs linked to clubhouse Phone #: ###-#### Inspection requested via web by Bob Stephens Underground to light poles and column signs ok to cover. Pole base grounding ok
Change Status to I  8/17/2016 DONE
Reopen permit per James A. Finaled by mistake
Final6/14/20166/15/20166/15/2016APASS
DetailsDaryl DeGrange
Final - reinspection Phone #: ###-#### Inspection requested via web by Bob Stephens correction done, final ok
Final6/13/20166/14/20166/14/2016PFAIL
DetailsDaryl DeGrange
Doug Phone #: ###-#### NEC 210.8(B)(2) All 15 and 20 ampere 120 volt receptacle within 6ft of a sink requires GCFI protection. NEC 406.8(9)(B)(1) Receptacles installed in wet locations shall be listed weather-resistant type.NEC 406.12 Child care facilities require tamper-resistant receptacles. NEC 422.52 Electric drinking fountains require GFCI protection
Permanent Service6/7/20166/8/20166/8/2016APASS
DetailsJames Ady
Doug Phone #: ###-#### p/s u/g n ok
Electrical Rough-In2/10/20162/11/20162/11/2016APASS
DetailsEric Story
Re inspect rough electrical on clubhouse Phone #: ###-#### Inspection requested via web by Bob Stephens clubhouse ok cover(electrical room not ready at this point will call for another inspection on later date)
Electrical Rough-In2/9/20162/10/20162/10/2016PNR
DetailsEric Story
Completion of Rough Electrical on the Club house Phone #: ###-#### Inspection requested via web by Bob Stephens still need securing of nm cable and emt not ready
Issue PAID IN FULL permit  2/9/2016 DONE
Payment received via Govolutions
Application received  2/9/2016 DONE
This permit was created on the web by Bob Stephens
Electrical Rough-In11/16/201511/17/201511/17/2015APASS
DetailsRock A. Hudson
Inspect pipe and floor plug boxes underground clubhouse-exercise room Phone #: ###-#### Inspection requested via web by Bob Stephens
West area 4 floor boxes and conuit feeding them rough in ok cover
First Notice1/25/20171/25/2017   
DetailsMark Moncarr