Final | 5/24/2016 | 5/25/2016 | 5/25/2016 | A | FAIL |
Eric Story
|
|
|
Inspection requested via web by steve ragan 314,25 cover required for man hole cover on light pole
|
Electrical Rough-In | 2/24/2016 | 2/25/2016 | 2/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
Rick-underground conduit-late AM Phone #: ###-#### Underground under road. 4 install for electrical with spare and sleeve for future sprinkler. Rough in ok cover
|
Electrical Rough-In | 2/12/2016 | 2/12/2016 | 2/12/2016 | P | FAIL |
Eric Story
|
|
|
Underground inspection Phone #: ###-#### Inspection requested via web by steve ragan underground going across road is to shallow must have 24" depth or encased in 2" of concrete(was never looked at. They did say it is but cannot verify it)
|
Electrical Rough-In | 2/12/2016 | 2/12/2016 | 2/12/2016 | P | PASS |
Eric Story
|
|
|
Underground inspection Phone #: ###-#### Inspection requested via web by steve ragan underground ok cover
|