Final | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | PASS |
Eric Story
|
|
|
GC put 2x4 and 2x6 to protect type NM cable final ok
|
Final | 4/21/2016 | 4/22/2016 | 4/22/2016 | A | CANC |
Eric Story
|
|
|
Access code is 6028. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot will call in for pm
|
Final | 4/21/2016 | 4/21/2016 | 4/21/2016 | P | FAIL |
Eric Story
|
|
|
This is a garage...access is 6028. Thank you. Phone #: ###-#### Inspection requested via web by Paula Gratiot not corrected at this time
|
Final | 4/18/2016 | 4/19/2016 | 4/19/2016 | A | FAIL |
Eric Story
|
|
|
This is a Garage. Access code is #6028. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot 334.15 type NM cable shall be protected from physical damage
|
Electrical Rough-In | 2/18/2016 | 2/19/2016 | 2/19/2016 | A | PASS |
Eric Story
|
|
|
This is Rough in of a detached garage. Builder # is ###-#### Zac Smith. Phone #: ###-#### Inspection requested via web by Paula Gratiot 300.4 bored holes within 1 1/4 of framing member shall have nail plate 230.71 service discconect shall not have more then 6 means of disconnects
|
Issue PAID IN FULL permit | | | 2/16/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/16/2016 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|