First Notice | 4/5/2016 | 4/5/2016 | 7/6/2016 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Stan Woodward
|
Final | 4/4/2016 | 4/5/2016 | 4/5/2016 | A | PASS |
Rex Boyles
|
|
|
Could we get this early Phone #: ###-#### Inspection requested via web by Stan Woodward corrections made final ok
|
Final | 4/2/2016 | 4/4/2016 | 4/4/2016 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Stan Woodward 210.62-At least one 120volt receptacle outlet shall be installed within 18" of top of show window for each 12 linear foot (6' or more) of show window. 220.14(G)(2)- 200 va per lineal foot of show window required. 422.31(A) and (B)- disconnect or lockoff on circuit breaker required permanently connected air pump machine
|
Electrical Rough-In | 3/30/2016 | 3/30/2016 | 3/30/2016 | P | PASS |
Rex Boyles
|
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by Stan Woodward T GRID CEILINGS OK
|
Permanent Service | 3/21/2016 | 3/22/2016 | 3/22/2016 | A | PASS |
Bob Reichert
|
|
|
Service for permanent power Phone #: ###-#### Inspection requested via web by Stan p/s u/g rec ok
|
Electrical Rough-In | 3/14/2016 | 3/14/2016 | 3/14/2016 | P | PASS |
Rex Boyles
|
|
|
Walls, Bathroom for cover Phone #: ###-#### Inspection requested via web by Stan Woodward r/i ok bathroom walls and ceilings, all walls to the east
|
Electrical Rough-In | 3/3/2016 | 3/3/2016 | 3/3/2016 | A | PASS |
Rex Boyles
|
|
|
Underground in the slab and about grounding new service Phone #: ###-#### Inspection requested via web by Stan Woodward r/i ok underslab raceways and floor boxes. ALSO Stan will install #4 bare copper for concrete encased electrode for new service
|
Issue PAID IN FULL permit | | | 2/22/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/22/2016 | | DONE |
|
|
|
This permit was created on the web by Stan Woodward
|