Final | 6/13/2016 | 6/14/2016 | 6/14/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean Corrections fixed final ok
|
Final | 6/2/2016 | 6/3/2016 | 6/3/2016 | A | FAIL |
Eric Story
|
|
|
Brad Phone #: ###-#### 210.8 receptacles in kitchens serving countertop shall have GFCI protection 334.15 type NM cable shall be protected from physical damage
|
Final | 5/29/2016 | 5/31/2016 | 5/31/2016 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean 210.52(c)(2) at least one receptacle shall be installed at each island
|
Electrical Rough-In | 3/11/2016 | 3/11/2016 | 3/11/2016 | P | PASS |
Rock A. Hudson
|
|
|
Kitchen rough in ok cover
|
Final | 3/10/2016 | 3/11/2016 | 3/11/2016 | A | CANC |
Rock A. Hudson
|
|
|
Inspect installation of 6 new can lights installed in teh kitchen. Phone #: ###-#### Inspection requested via web by Spencer McLean Needed rough in inspection.
|
Electrical Rough-In | 3/11/2016 | 3/11/2016 | 3/11/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Inspect installation of 6 new can lights installed in teh kitchen. Phone #: ###-#### Inspection requested via web by Spencer McLean 210.52- Shall have a receptacle outlet installed with in 24"of right side of range to serve counter top space. 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface.
|
Issue PAID IN FULL permit | | | 3/10/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/10/2016 | | DONE |
|
|
|
This permit was created on the web by Spencer McLean
|