Final | 10/17/2016 | 10/17/2016 | 10/17/2016 | P | PASS |
Rock A. Hudson
|
|
|
corrections have been made call josh @ ###-#### for access some one staying there now Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
|
Final | 9/26/2016 | 9/27/2016 | 9/27/2016 | A | FAIL |
Eric Story
|
|
|
sorry about mix up there is key under matt at back door the building is unoccupied was there before but if problem please call will be close to phone Phone #: ###-#### Inspection requested via web by dennis mcneely 406.5 receptacles shall be rigidly mounted(through out house) 334.12 Type NM cable shall not exposed where subject to physical damage(understairs) 422.30 Lockout required for dishwasher/water heater 210.8 (a)(5) portins of unfinished basements shall have GFCI protection(furnace receptacle)
|
Final | 9/21/2016 | 9/21/2016 | 9/21/2016 | P | CANC |
Eric Story
|
|
|
Call for access // Dennis Phone #: ###-#### no access called and left message will need it called back in
|
Electrical Rough-In | 3/20/2016 | 3/21/2016 | 3/21/2016 | P | PASS |
Rex Boyles
|
|
|
cover inspection - if no one there key will be under stair under rock back door but someone should be Phone #: ###-#### Inspection requested via web by dennis mcneely r/i all new wiring ok bdrm. and liv. rm. walls not opened up.. existing receptacle spacing ok
|
Issue PAID IN FULL permit | | | 3/20/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/20/2016 | | DONE |
|
|
|
This permit was created on the web by dennis mcneely
|