Final | 4/11/2016 | 4/11/2016 | 4/11/2016 | P | PASS |
Eric Story
|
|
|
George Phone #: ###-#### correction fixed solar array final ok
|
Final | 4/8/2016 | 4/11/2016 | 4/11/2016 | A | FAIL |
Eric Story
|
|
|
Call to meet on site. Phone #: ###-#### Inspection requested via web by Thaniel Bishop 240.4 (d)(7) #10 awg shall not have a OCPD larger then 30 ampere
|
Electrical Rough-In | 4/7/2016 | 4/8/2016 | 4/8/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Thaniel Bishop verified solar array install with u/l listings and scope of work
|
Issue PAID IN FULL permit | | | 3/22/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/22/2016 | | DONE |
|
|
|
This permit was created on the web by Thaniel Bishop
|