Final | 5/27/2016 | 5/27/2016 | 5/27/2016 | P | PASS |
Rock A. Hudson
|
|
|
Corrections made. Final ok
|
Final | 5/26/2016 | 5/27/2016 | 5/27/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Call John Binfet for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg 210.8(B)- Receptcle outlet located within 6' of sink in old kitchen area shall have GFCI protection. *Receptacle outlets in basement not working.
|
Final | 3/31/2016 | 3/31/2016 | 3/31/2016 | P | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg needed r/i
|
Electrical Rough-In | 3/31/2016 | 3/31/2016 | 3/31/2016 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg corrections made r/i ok
|
Electrical Rough-In | 3/30/2016 | 3/31/2016 | 3/31/2016 | A | FAIL |
Rex Boyles
|
|
|
Key located in mail box slot at front door Phone #: ###-#### Inspection requested via web by jamie berg 300.4(A)(1)- 11/4" required from bored holes to edge of stud. nailplates required. see list on correction notice
|
Issue PAID IN FULL permit | | | 3/30/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/30/2016 | | DONE |
|
|
|
This permit was created on the web by jamie berg
|
First Notice | 5/27/2016 | 5/27/2016 | | | |
Rock A. Hudson
|
|
|
|