Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE16-01160
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 110 N 11TH ST
Project NameSumner Trust - Vanilla T.I.
Customer Number17225
ePlanReviewNo
Description
Alteration: 100 AMP PERMANENT SERVICE-see ELE15-03516 for work that was started on this project and Tri-Sate finished the job
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (ELE)  12/27/2016 DONE
First Notice5/3/20165/3/201611/17/2016 DONE
DetailsRex Boyles
as per GC electrical valuation that was paid for both ele permits was $3113.00. As per Dan with Mountain Valley Electric ELE15-03516-they did not get paid for the part of the work they did-Tri-State took over job after the rough in
Final5/2/20165/3/20165/3/2016APASS
DetailsRex Boyles
Contact: Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden final ok
Permanent Service5/3/20165/3/20165/3/2016PPASS
DetailsRex Boyles
Contact: Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden p/s u/g n ok existing service, add 1 phase meter to 3 phase system. available fault current for existing service exceeds AIC rating.
Final4/29/20164/29/20164/29/2016PCANC
DetailsRex Boyles
Contact: Derrick Kamper Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
Final4/12/20164/13/20164/13/2016ACANC
DetailsRex Boyles
final for permanent service.
Your contact name will be Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden needed r/i p/s
Electrical Rough-In4/13/20164/13/20164/13/2016PPASS
DetailsRex Boyles
final for permanent service.
Your contact name will be Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden new 100amp service ,feeder and loadcenter ok NOTE:need available fault current label on new main disconnect as per NEC 110.24 and re label all services with addresses service 1 of 5,service 2 of 5 and so on for fire dept. prior to energizing new service.
Issue PAID IN FULL permit  4/12/2016 DONE
Payment received via Govolutions
Application received  4/12/2016 DONE
This permit was created on the web by Deb Gooden