Final | 8/17/2016 | 8/18/2016 | 8/18/2016 | A | PASS |
Eric Story
|
|
|
Gail or Craig Phone #: ###-#### final for shop ok
|
Final | 8/11/2016 | 8/12/2016 | 8/12/2016 | A | FAIL |
Eric Story
|
|
|
Gil Phone #: ###-#### 406.4 outside receptacles shall be weather resistant type 210.8 all 120v receptacles shall have GFCI protection and be readily accessible 352.30 PVC shall be secured wihin 36" of a box
|
Electrical Rough-In | 7/21/2016 | 7/22/2016 | 7/22/2016 | A | PASS |
James Ady
|
|
|
Craig Phone #: ###-#### Talked to home owner about the need for tamper resistant recepticles/ Weather resistant in WP, And need for GFCI breakers in panel not AFCI Rough in ok
|
Permanent Service | 7/7/2016 | 7/7/2016 | 7/7/2016 | P | CANC |
Eric Story
|
|
|
Gail Phone #: ###-#### permanent service was already inspected will final on shop final to verify proper wiring to feed the shop
|
Electrical Rough-In | 5/16/2016 | 5/17/2016 | 5/17/2016 | A | PASS |
Bob Reichert
|
|
|
underground; Gale Phone #: ###-#### ok cover u/g house to garage
|
Conference | 5/2/2016 | 5/9/2016 | 5/9/2016 | A | DONE |
Rock A. Hudson
|
|
|
Gail Phone #: ###-#### Discussed code requirements for new shop. Informed owner of tamper resistant, GFCI grounding electrode and conduit depth requirements.
|
Application received | | | 4/15/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/15/2016 | | DONE |
|
|
|
|