Final | 5/26/2016 | 5/27/2016 | 5/26/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn correction fixed final ok
|
Final | 5/26/2016 | 5/26/2016 | 5/26/2016 | P | PASS |
Eric Story
|
|
|
###-#### Correction fixed final ok
|
Final | 5/25/2016 | 5/26/2016 | 5/26/2016 | A | NH |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn House locked no garage door key pad. called for key location left message.
|
Final | 5/25/2016 | 5/25/2016 | 5/25/2016 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.7 Wiring integrity kitchen lights in-op 406.5 Receptacles shall be rigidly mounted(recept in garage loose)
|
Rough-In Permanent Service | 4/25/2016 | 4/26/2016 | 4/26/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 4/22/2016 | 4/25/2016 | 4/25/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 250.28- Main bonding jumper shall be installed. Bonding screw. 300.4- NM cable shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface. Above panel, dn west bed, up center bed. 330.30- Secure and support NM cable. Supports shall not exceed 4 1/2' above living window. Secure up master stool switch and secure NM cable within 12" of box.
|
Issue PAID IN FULL permit | | | 4/21/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/21/2016 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|