First Notice | 5/5/2016 | 5/5/2016 | 6/8/2016 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Celinda Winters
|
Temporary Service | 5/5/2016 | 5/5/2016 | 5/5/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Winters T/S U/G N OK
|
Temporary Service | 5/3/2016 | 5/4/2016 | 5/4/2016 | A | FAIL |
Bob Reichert
|
|
|
Temporary power pole for ACHD pump control panel. Phone #: ###-#### Inspection requested via web by Brandon Winters called, left correction notice, NEC 406.9(B) receptacles shall be listed WR type and shall have in-use cover installed, 408.4 shall provide correct circuit directory, 110.12(A) shall close unused openings in panel, BCC shall post job id sticker, use listed equipment-ground lug
|
Issue PAID IN FULL permit | | | 5/3/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/3/2016 | | DONE |
|
|
|
This permit was created on the web by Brandon Winters
|