First Notice | 6/3/2016 | 6/3/2016 | 2/14/2017 | | DONE |
Eric Story
|
|
|
|
Final | 6/3/2016 | 6/3/2016 | 6/3/2016 | P | PASS |
Eric Story
|
|
|
Requesting a Electrical Final for Core/Shell Thanks Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence Correction fixed final ok
|
Final | 6/1/2016 | 6/3/2016 | 6/3/2016 | A | FAIL |
Eric Story
|
|
|
Request Electrical Final Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence 314.25 in complete installations boxes shall hae covers (need blanks in un-occupied space )
|
Permanent Service | 5/12/2016 | 5/13/2016 | 5/13/2016 | P | PASS |
James Ady
|
|
|
Electrical Service Inspection. Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence p/s u/g n ok
|
Permanent Service | 5/11/2016 | 5/12/2016 | 5/12/2016 | A | FAIL |
James Ady
|
|
|
Electrical Inspection for Permanant Service. Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence 110.24 Service equipment in other than dwelling units, Available fault current shall be legibly marked in the feild
|
Issue PAID IN FULL permit | | | 5/11/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/11/2016 | | DONE |
|
|
|
This permit was created on the web by Tim Lawrence
|