Final | 5/27/2016 | 5/31/2016 | 5/31/2016 | A | PASS |
Eric Story
|
|
|
Dale Phone #: ###-#### Corrections fixed final ok
|
Final | 5/26/2016 | 5/27/2016 | 5/27/2016 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew White 408.41 Grounded conductor shall terminate within a panelboard in a individual terminal 230.71 Maximun number of DIsc. shall not be greater then 6 without a main disc. 250 no bonding jumper and isolate grounding and grounded condutor 225.38 main disc means required for seperate structure and shall be held in place as per 408.36(d)
|
Issue PAID IN FULL permit | | | 5/12/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/12/2016 | | DONE |
|
|
|
This permit was created on the web by Matthew White
|