Final | 3/20/2017 | 3/21/2017 | 3/21/2017 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor Corrections fixed final ok
|
Final | 3/19/2017 | 3/20/2017 | 3/20/2017 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor 110.21 Open ground on quad upstairs 110.25 Lockout required for dishwasher 210.12 AFCI protection required for all beds 406.12 Up bath needs tamper resistant 406.4 All exterior receptacles shall be weather resistant type
|
Electrical Rough-In | 10/6/2016 | 10/7/2016 | 10/7/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor Kitchen,back becks and bath , all upstairs ok cover
|
Rough-In Permanent Service | 9/22/2016 | 9/23/2016 | 9/23/2016 | A | CANC |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor only needed conference&p/s
|
Permanent Service | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor p/s o/h n ok
|
Conference | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | DONE |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Nathan Taylor Discussed code requirements forAFCI/GFCI and tamper resistent receptacles, walked about outlet layouts in beds and bath, Also discussed have some kind of retaining clip for back fed main breaker he will either replace panel or find a listed clip
|
Application received | | | 5/13/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/13/2016 | | DONE |
|
|
|
|