Print Statement | | | 8/30/2017 | | DONE |
|
|
|
sent 3rd late notice
|
Print Statement | | | 6/15/2017 | | DONE |
|
|
|
sent 2nd late notice
|
Print Statement | | | 4/20/2017 | | DONE |
|
|
|
sent 1st late final value
|
Print Statement | | | 12/5/2016 | | DONE |
|
|
|
|
Final | 10/5/2016 | 10/5/2016 | 10/5/2016 | P | PASS |
Tom Saunders
|
|
|
Mark Phone #: ###-####
no corrections needed...ok to final
|
Electrical Rough-In | 9/20/2016 | 9/20/2016 | 9/20/2016 | P | PASS |
Tom Saunders
|
|
|
Mark Phone #: ###-####
OK TO COVER...BATH REMODEL - SWITCHING ADDED
|
Final | 9/13/2016 | 9/14/2016 | 9/14/2016 | A | NR |
Eric Story
|
|
|
Mark Phone #: ###-#### not ready
|
Electrical Rough-In | 8/18/2016 | 8/18/2016 | 8/18/2016 | P | PASS |
Eric Story
|
|
|
Mark Phone #: ###-#### ceilings only ok cover
|
Electrical Rough-In | 8/15/2016 | 8/16/2016 | 8/16/2016 | A | FAIL |
Eric Story
|
|
|
Mark-ceiling grid Phone #: ###-#### 110.12 unused openings shall be closed 314.25 covers needed
|
Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 | A | PASS |
Rock A. Hudson
|
|
|
Mark-partial interior walls Phone #: ###-#### Discussed GFCI device shall be readily accessible for operational jetted tubs. 1st floor wall rough in ok cover
|
Electrical Rough-In | 5/25/2016 | 5/26/2016 | 5/26/2016 | A | PASS |
Eric Story
|
|
|
underground; Mark Phone #: ###-#### undergroud for showroom ok cover
|
Application received | | | 5/16/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/16/2016 | | DONE |
|
|
|
|
First Notice | 10/5/2016 | 10/5/2016 | | | |
Tom Saunders
|
|
|
|