Final | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Rock A. Hudson
|
|
|
Unit 203 , re-inspect planter recepts should be last final inspection, ready for sign off Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Final ok
|
Final | 8/29/2017 | 8/30/2017 | 8/30/2017 | A | PART |
Eric Story
|
|
|
Units 210 , 202 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Units 210,202 ok to occupy
|
Final | 8/22/2017 | 8/22/2017 | 8/22/2017 | A | PART |
Rock A. Hudson
|
|
|
Unit 106 and Finish 105 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Rooms noted TCO ok
|
Final | 8/18/2017 | 8/21/2017 | 8/21/2017 | A | PART |
Rock A. Hudson
|
|
|
unit 105,107 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 107 bath GFI in op and kitchen not complete. 105 TCO ok
|
Final | 8/10/2017 | 8/11/2017 | 8/11/2017 | A | PART |
Rock A. Hudson
|
|
|
Live works 103 and 104 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Rooms as noted on print but actual labels different. TCO ok
|
Electrical Rough-In | 6/26/2017 | 6/26/2017 | 6/26/2017 | P | PASS |
Rock A. Hudson
|
|
|
Drop ceilings 211 , 212 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted rough in ok cover
|
Electrical Rough-In | 6/22/2017 | 6/22/2017 | 6/22/2017 | P | PASS |
Mark Moncarr
|
|
|
Drop Ceilings Town house 111 , 112 , 113 , 213 Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover bath ceilings and EVU's in rooms 111-113 and 213
|
Final | 6/21/2017 | 6/21/2017 | 6/21/2017 | P | PART |
Rock A. Hudson
|
|
|
Unit 208 Phone #: ###-#### Inspection requested via web by Tom Betty 208 TCO ok
|
Final | 6/20/2017 | 6/20/2017 | 6/20/2017 | P | PART |
James Ady
|
|
|
unit 305 studio , amenities , unit 208 Phone #: ###-#### Inspection requested via web by Tom Betty 208 not ready. 305 , Amenities ok. Corrections made 204,203 and 602.
|
Final | 6/19/2017 | 6/19/2017 | 6/19/2017 | P | PART |
Rock A. Hudson
|
|
|
Final inspections for units #203 and #204 and Studio #305. Contact Craig Timmons Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 305 not ready, mini split fusing ok, heater covers installed, 2nd elevator lobby receptacles ok, 603 owner wanted walk in tub with out electrical hooked up, 203, 204, 603 only TCO ok
|
Final | 6/16/2017 | 6/16/2017 | 6/16/2017 | P | PART |
Rock A. Hudson
|
|
|
Afton Contact Craig Timmons ###-#### Finals on Stairway #3 Lobbies on the 1st and 2nd floors Units 601,602,603, and 604 All Trash rooms.
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek Mini-split smaller units fusing 20 max, out receptacle on motion sensor com rm, planter receptacles locate out of soil, Heat trace not in, EPD breakers installed, Heater covers to install in trash rooms 3-6, Check elevator lobby receptacles, off, 603 GFCI protection for walk in tub, 602 Island receptacles need installed. Not completed- Live/works office areas to remain vanilla space, Live works appartments 203, 204, 208. Town house units 111, 112, 113, 211, 212, 213. Elevators not complete. Completed- Out egress, Stair 1,2,3, Garages 1,2, Corridors 3,4,5,6, 301 thru 304, 401 thru 405, 501 thru 505, 601,604,605, lobby 1,2. TCO for areas noted complete.
|
Final | 6/15/2017 | 6/15/2017 | 6/15/2017 | P | NR |
Rock A. Hudson
|
|
|
Units 503 , 504 , 505 , 605 , Roof Phone #: ###-#### Inspection requested via web by Tom Betty Out receptacle roof com room switched by photo cell, Fuse smaller HVAC units to 20 amp noted on name plate, all outdoor receptacles on roof shall have in-use covers. Rooms noted checked OK.
|
Final | 6/14/2017 | 6/14/2017 | 6/14/2017 | P | NR |
Rock A. Hudson
|
|
|
Re-inspect 401 and inspect 501 , 502 Corridor 3rd , 4th , 5th , 6th , Garage 1st 2nd and stairs #1 , #2 Phone #: ###-#### Inspection requested via web by Tom Betty Checked 401, 501, 502, level 1 trash rm, level 2 storage rm, bike rm OK, Corridors duplex receptacles shall be WR as per 406, Planter receptacles shall not be in soil, Check flexible cord on garage door opener, stair 3 NR, lobbies NR
|
Final | 6/12/2017 | 6/13/2017 | 6/13/2017 | A | PEND |
Rock A. Hudson
|
|
|
Re-inspect 301 , 302 , 303 ,304 , 402 , 403 , 404 and finals on 401 , 405 Phone #: ###-#### Inspection requested via web by Tom Betty 401 had receptacles not working in family, and halls. 301 thru 304 and 402 thru 405 checked out OK. TCO pending stairways, out egress, core and shell areas approval
|
Final | 6/8/2017 | 6/8/2017 | 6/8/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Just units 301,302,303,304,402,403,404 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 4-05-24 Inspection required on all floor heat installions. 210.52(B)- Kitchen counter top areas shall have a receptacle outlet with 24" of edge of counter. counter off dining area 1 receptacle on left of 48" counter top. 250.140- Dryers in units shall have grounded and grounding terminations seperated. In cord junction 2 white grounded present, 1 terminated with neutral and 1 with ground. 410.16(C)- Closet luminaires, for recessed 6" minimum clearance from storage shelf, for surface LED 12" clearance required. Several unit too close. 422.11(A)- Water heaters shall be fused to manufacturers specs. 60 amp installed on 25 amp recommended fusing. 422.30- A disconnecting means shall be provided to disconnect ungrounded from appliances. Water heaters and range hoods. Unit 403 deck receptacle not trimmed.
|
Electrical Rough-In | 5/9/2017 | 5/9/2017 | 5/9/2017 | P | PASS |
Mark Moncarr
|
|
|
About 100 feet of trench Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover. 2 runs of 1" to 2 pole lights on S side of building.
|
Electrical Rough-In | 5/2/2017 | 5/3/2017 | 5/3/2017 | A | PASS |
Rock A. Hudson
|
|
|
Garden Shed and drop ceiling 305 Suite and 307 amenities Phone #: ###-#### Inspection requested via web by Tom Betty Garden shed wiring must be covered prior to weater. Rough in ok cover
|
Electrical Rough-In | 4/11/2017 | 4/11/2017 | 4/11/2017 | A | PASS |
Rock A. Hudson
|
|
|
Inspect drop ceiling and reinspect fire pump service Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty East soffit cans and lobby grid rough in ok cover
|
Permanent Service | 4/11/2017 | 4/11/2017 | 4/11/2017 | P | PASS |
Rock A. Hudson
|
|
|
Inspect drop ceiling and reinspect fire pump service Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Fire pump p/s u/g n ok
|
Permanent Service | 3/13/2017 | 3/13/2017 | 3/13/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Firepump service. 695.4- Overcurrent device shall carry indefinately locked rotor current. 400 installed 500 amp min. Contractor to change to 600 amp knife switch. 695.6- Wiring method to jockey pump shall be one listed, standard MC cable not listed.
|
Permanent Service | 3/10/2017 | 3/13/2017 | 3/13/2017 | A | PASS |
Rock A. Hudson
|
|
|
Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Fire pump service not included. 30 single phase meters, 2 3 phase meters. p/s u/g n ok
|
Electrical Rough-In | 3/1/2017 | 3/2/2017 | 3/2/2017 | A | PASS |
Rock A. Hudson
|
|
|
Town house 112 and 1st and 2nd floor lobby Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted walls and hardlids rough in ok cover
|
Electrical Rough-In | 2/21/2017 | 2/22/2017 | 2/22/2017 | A | PASS |
Eric Story
|
|
|
Drop ceilings 602,603,and 604 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Ceiliings in units 602,603,604 hard lids ok cover
|
Electrical Rough-In | 2/20/2017 | 2/21/2017 | 2/21/2017 | A | PART |
Rock A. Hudson
|
|
|
Drop ceiling 601,602,603,604,605,bike room area and comm room on roof call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 103, 104, 109 walls and hardlids, 601, 605 only drop ceilings, bike rm, 1,2 storage rms, comm room roof rough in ok cover
|
Electrical Rough-In | 2/16/2017 | 2/16/2017 | 2/16/2017 | A | PASS |
Rock A. Hudson
|
|
|
Town house 211,212,213 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Check for lights in storage rooms. Areas noted rough in ok cover
|
Electrical Rough-In | 1/30/2017 | 1/30/2017 | 1/30/2017 | A | PASS |
Rock A. Hudson
|
|
|
Reinspect storage walls and stairwell #3 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Storage rm and corridor, and stair 3 walls 2nd floor rough in ok cover
|
Electrical Rough-In | 1/25/2017 | 1/26/2017 | 1/26/2017 | A | PART |
Rock A. Hudson
|
|
|
Storage room , comm room and some entry room walls Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 2nd floor corridor to storage remove drywall that was installed prior to inspection. 2nd floor areas noted rough in ok cover
|
Electrical Rough-In | 1/18/2017 | 1/19/2017 | 1/19/2017 | A | PASS |
Rock A. Hudson
|
|
|
Drop ceiling room 208 and some walls in entry call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 208 and hall off pet wash and stair 1 side rough in ok cover
|
Electrical Rough-In | 1/5/2017 | 1/6/2017 | 1/6/2017 | A | PASS |
Rock A. Hudson
|
|
|
Three drop ceilings call craig Phone #: ###-#### Inspection requested via web by Tom Betty
503, 504, 505 drop ceiling rough in ok cover
|
Electrical Rough-In | 12/14/2016 | 12/14/2016 | 12/14/2016 | A | PASS |
Rock A. Hudson
|
|
|
Some drop ceilings and couple walls call craig Phone #: ###-#### Inspection requested via web by Tom Betty 112 ADA not ready check panel height. 111, 113 town houses, 203, 204, 405, 501, 502 drop lids, 504, 504 firewall rough in ok cover
|
Electrical Rough-In | 11/29/2016 | 11/30/2016 | 11/30/2016 | A | PASS |
Rock A. Hudson
|
|
|
Four drop ceilings Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Units 401, 402, 403, 404 drop ceilings rough in ok cover
|
Electrical Rough-In | 11/17/2016 | 11/18/2016 | 11/18/2016 | A | PASS |
Eric Story
|
|
|
Inspect 3rd floor stair landing in stairwell 1 and 2 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty stair 1@2 protection of MC ok
|
Electrical Rough-In | 11/16/2016 | 11/17/2016 | 11/17/2016 | A | PASS |
Eric Story
|
|
|
Stairs and corridors.Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Stairs 1@2,trash rooms,corridors,data room,storage ok cover. EC will call another rough-in in for MC wrapped around metal beams, will install in a raceway to protect from physical damage. Inspection will .be 11-18-16
|
Electrical Rough-In | 10/24/2016 | 10/25/2016 | 10/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
Unit 601 and one wall Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Unit 601 and firewall in 304 rough in ok cover
|
Electrical Rough-In | 10/7/2016 | 10/14/2016 | 10/14/2016 | P | PASS |
Rock A. Hudson
|
|
|
Four units will be ready Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Units 208, 602, 603, 604, 605, firewalls to be done in future. walls and hardlids rough in ok cover
|
Electrical Rough-In | 10/6/2016 | 10/6/2016 | 10/6/2016 | A | PASS |
Rock A. Hudson
|
|
|
One unit ready Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Unit 203 only walls only rough in ok cover
|
Electrical Rough-In | 9/27/2016 | 9/28/2016 | 9/28/2016 | P | PASS |
Eric Story
|
|
|
Need 4 to 5 units Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty room 240 and 5th floor rooms walls only ok cover (wall with house panels will need to be looked at once complete)
|
Conference | 9/21/2016 | 9/21/2016 | 9/21/2016 | P | DONE |
Mark Moncarr
|
|
|
Had talked to Rock about access to split system heating above hard lid with access door.Need some clarification on working accessibility. Phone #: ###-#### Inspection requested via web by Tom Betty Manufacturers specs call for minimum 18" of working clearance for access panel.
|
Electrical Rough-In | 9/13/2016 | 9/14/2016 | 9/14/2016 | A | PASS |
Eric Story
|
|
|
Four to Five units ready , Craig Phone #: ###-#### Inspection requested via web by Tom Betty 304(exept west wall,once furred out will need to looked at)3rd floor ammendities and suite (exept east and north wall) 403,404 (except west wall) 405 ok cover
|
Electrical Rough-In | 9/2/2016 | 9/6/2016 | 9/6/2016 | P | PASS |
Mark Moncarr
|
|
|
Will have 4 to 5 units ready.call Craig Phone #: ###-#### Inspection requested via web by Tom Betty ok to cover rms 301, 302, 303, 401, 402
|
Conference | 7/14/2016 | 7/15/2016 | 7/15/2016 | A | PASS |
Rock A. Hudson
|
|
|
Discuss use of romex in all condo''s with Craig Phone #: ###-#### Inspection requested via web by Tom Betty Discussed use of NM cable in condos. Building permit noted type V construction. NM cable shall have at least 15 minute fire barrier and not be installed above drop or grid ceilings as per NEC 334.10. Also mentioned access to HVAC unit control boxes shall have room to access.
|
Issue PAID IN FULL permit | | | 5/25/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 5/25/2016 | | |
|
|
|
|
Application received | | | 5/25/2016 | | DONE |
|
|
|
This permit was created on the web by Cathy Duchek
|
First Notice | 9/6/2017 | 9/6/2017 | | | |
Rock A. Hudson
|
|
|
|