Temporary Service | 6/6/2016 | 6/6/2016 | 6/6/2016 | P | PASS |
Eric Story
|
|
|
Need another one as we had to fix something. Phone #: ###-#### Inspection requested via web by Vicki Moore correction fixed t/s o/h n ok
|
Temporary Service | 6/3/2016 | 6/6/2016 | 6/6/2016 | A | FAIL |
Eric Story
|
|
|
Call Travis with any questions Phone #: ###-#### Inspection requested via web by Vicki Moore 240.24 no over current device shall be located higher then 6'-7" 100 amp breaker not rated where it is installed 110.26 shall maintain 36"working clearences in front of panel need address changed to 1550 W idaho street
|
Issue PAID IN FULL permit | | | 6/2/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/2/2016 | | DONE |
|
|
|
This permit was created on the web by Vicki Moore
|
First Notice | 6/6/2016 | 6/6/2016 | | | |
Eric Story
|
|
|
|