Permanent Service | 6/13/2016 | 6/13/2016 | 6/13/2016 | P | CANC |
Bob Reichert
|
|
|
Jake Phone #: ###-#### see t/s
|
Temporary Service | 6/13/2016 | 6/13/2016 | 6/13/2016 | P | PASS |
Bob Reichert
|
|
|
Jake Phone #: ###-#### t/s o/h n ok
|
Temporary Service | 6/10/2016 | 6/10/2016 | 6/10/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Jake Westenskow is electrician on site Phone #: ###-#### Inspection requested via web by Kevin Perez 400.5- SOOW 10-4 flexible cord max overcurrent rating 25 amps, 50 amp installed. 590.6- All power other than 120 volt for receptacles shall have GFCI protection.
|
Issue PAID IN FULL permit | | | 6/9/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/9/2016 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|
First Notice | 6/13/2016 | 6/13/2016 | | | |
Bob Reichert
|
|
|
|