Final | 7/19/2016 | 7/20/2016 | 7/20/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale Final ok
|
Final | 7/18/2016 | 7/19/2016 | 7/19/2016 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale 406.6 faceplates required(in cabinet) 314.20 receptacles behind combustile material shall have a listed extender(in cabinet) 110.12(a) unused openings shall be closed(cieling)
|
Final | 6/20/2016 | 6/21/2016 | 6/21/2016 | P | CANC |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale Needed r/i
|
Electrical Rough-In | 6/21/2016 | 6/21/2016 | 6/21/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale reception area walls only ok cover
|
Final | 6/17/2016 | 6/17/2016 | 6/17/2016 | P | CANC |
Eric Story
|
|
|
final for electrical on the remodel Phone #: ###-#### Inspection requested via web by Shane Dale Needed r/i
|
Electrical Rough-In | 6/17/2016 | 6/17/2016 | 6/17/2016 | P | FAIL |
Eric Story
|
|
|
final for electrical on the remodel Phone #: ###-#### Inspection requested via web by Shane Dale 348.30 FMC shall be securely fastened within 12" of a box and not exceed 4 1/2' 300.4(2) notches in wood where a cable is ran through it shall have a listed nail plate to protect form physical damage
|
Issue PAID IN FULL permit | | | 6/13/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/13/2016 | | DONE |
|
|
|
This permit was created on the web by Shane Dale
|
First Notice | 7/20/2016 | 7/20/2016 | | | |
James Ady
|
|
|
|