First Notice | 6/27/2016 | 6/27/2016 | 7/26/2016 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Sean Patton
|
Final | 6/26/2016 | 6/27/2016 | 6/27/2016 | A | PASS |
Eric Story
|
|
|
Re-inspection on store front cord drops. Adjusted to meet 400.8. Boxes are suspended from strut by all thread and locking hardware. Strut is secured to framing members in ceiling. Phone #: ###-#### Inspection requested via web by Sean Patton corrections fixed final ok
|
Final | 6/24/2016 | 6/24/2016 | 6/24/2016 | P | FAIL |
Eric Story
|
|
|
Added 2 new SO cord drops at store front end. Fed from panel H CKT''s 40,42. Ran new 1/2'' raceway from panel to location. Cords are secured above ceiling with strain relief support grips. I will be out of town but can address any questions by phone. Have pictures taken during installation. Phone #: ###-#### Inspection requested via web by Sean Patton 400.8 flexible cords shall not be allowed above suspended cielings
|
Issue PAID IN FULL permit | | | 6/23/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/16/2016 | | DONE |
|
|
|
This permit was created on the web by Sean Patton
|