Final | 3/6/2017 | 3/7/2017 | 3/7/2017 | A | PASS |
Tom Saunders
|
|
|
Call half hour before to meet // Zack Phone #: ###-####...
ok to final
|
Electrical Rough-In | 6/22/2016 | 6/23/2016 | 6/23/2016 | A | PASS |
James Ady
|
|
|
Zach Phone #: ###-#### Corrections made Rough in ok to cover
|
Electrical Rough-In | 6/21/2016 | 6/22/2016 | 6/22/2016 | A | FAIL |
James Ady
|
|
|
Please call ahead for access - Zach Phone #: ###-#### 334.30 Securing NM cable within 12" of a box and every 4 1/2ft. 300.4 Wire throu bored holes less than 1 1/4in shall be protected. 300.4 D Cable ran parralel to framing shall be supported 1 1/4in from outside edge of framing. Discussed arc fault protection in bedrooms and tamper resistant outlets.
|
Issue PAID IN FULL permit | | | 6/21/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2016 | | DONE |
|
|
|
This permit was created on the web by zachariah Brown
|