Final | 8/5/2016 | 8/5/2016 | 8/5/2016 | P | PASS |
Rock A. Hudson
|
|
|
Contractor moved vent pipe installed in front of electrical service. Site ready for re-inspection. Russell Steadman is contact @ ###-####. Phone #: ###-#### Inspection requested via web by Todd Alder Final ok
|
Final | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | FAIL |
Rock A. Hudson
|
|
|
###-####- Called and re-opened permit. Wood support installed for vent pipe support installed in work space for electrical service. 110.26- Minimum of 30" wide and 36" deep shall be provided for service.
|
Change Status to I | | | 8/4/2016 | | DONE |
|
|
|
as per Rock Hudson; re-open permit
|
Final | 7/19/2016 | 7/19/2016 | 7/19/2016 | P | PASS |
Rock A. Hudson
|
|
|
Final inspection for lift station. Call Russell @ ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder Contractor confirmed seal offs have been poured. Final ok
|
Permanent Service | 7/5/2016 | 7/5/2016 | 7/5/2016 | P | PASS |
James Ady
|
|
|
Underground service for City of Boise Sewer Liftstation - Matt Miller @ ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder p/s u/g n ok
|
Issue PAID IN FULL permit | | | 6/29/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/29/2016 | | DONE |
|
|
|
This permit was created on the web by Todd Alder
|
First Notice | 8/5/2016 | 8/5/2016 | | | |
Rock A. Hudson
|
|
|
|
First Notice | 7/19/2016 | 7/19/2016 | | | |
Rock A. Hudson
|
|
|
|