Final | 9/20/2016 | 9/21/2016 | 9/21/2016 | A | PASS |
Eric Story
|
|
|
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
|
Permanent Service | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | PASS |
Eric Story
|
|
|
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan correction fixed, proper labels will be installed for final p/s o/h rec ok
|
Permanent Service | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | FAIL |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan 110.14- Dissimilar metals shall not be in contact with each other. 110.22- Each disconnecting means shall be identified as to it purpose.
|
Rough-In Permanent Service | 7/18/2016 | 7/19/2016 | 7/19/2016 | A | NR |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared at ###-####. Thank You!!! Phone #: ###-#### Inspection requested via web by Clay Morgan Service not ready
|
Electrical Rough-In | 7/19/2016 | 7/19/2016 | 7/19/2016 | P | PASS |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared at ###-####. Thank You!!! Phone #: ###-#### Inspection requested via web by Clay Morgan rough in ok cover
|
Meeting | | | 7/15/2016 | | DONE |
|
|
|
as per Rita-ok to attach all 4 ele permits to this building permit since they're all for the same burn project on a 4 plex
|
Issue PAID IN FULL permit | | | 7/7/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2016 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|