Final | 9/23/2016 | 9/26/2016 | 9/26/2016 | A | PASS |
Eric Story
|
|
|
lock box code is 4750. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections fixed final ok
|
Final | 9/20/2016 | 9/21/2016 | 9/21/2016 | A | FAIL |
Eric Story
|
|
|
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan 110.26 working space clearences required for electrical equipment 110.25 Lockout required for hard wired appliances 210.8 GFCI protection required for exterior outlets and will be WR type and in-use type
|
Permanent Service | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | PASS |
Eric Story
|
|
|
If you have any questions, please call Jared ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan correction fixed, proper labels will be in place for final p/s o/h rec ok
|
Permanent Service | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | FAIL |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan 110.14- Dissimilar metals shall not be in contact with each other. 110.22- Each disconnecting means shall be identified as to it purpose.
|
Electrical Rough-In | 7/15/2016 | 7/15/2016 | 7/15/2016 | P | PASS |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared ###-####. Thank You! Phone #: ###-#### Inspection requested via web by Clay Morgan Called to attach to BLD16-01557. Unit 2277 rough in ok cover
|
Meeting | | | 7/15/2016 | | DONE |
|
|
|
as per Rita-ok to attach all 4 ele permits to this building permit since they're all for the same burn project on a 4 plex
|
Issue PAID IN FULL permit | | | 7/7/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2016 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|