Final | 9/20/2016 | 9/20/2016 | 9/20/2016 | P | PASS |
James Ady
|
|
|
ready now. code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
Rough-In Permanent Service | 8/5/2016 | 8/8/2016 | 8/8/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
Electrical Rough-In | 7/12/2016 | 7/12/2016 | 7/12/2016 | P | PASS |
Bob Reichert
|
|
|
corrections made, ok backfill
|
Electrical Rough-In | 7/11/2016 | 7/12/2016 | 7/12/2016 | A | FAIL |
Bob Reichert
|
|
|
this is for the concrete encased electrode. Phone #: ###-#### Inspection requested via web by Bob Glenn called, left correction notice, NEC 250.52(A)(3) shall encase minimum 20' concrete and bare copper
|
Electrical Rough-In | 7/11/2016 | 7/11/2016 | 7/11/2016 | P | PASS |
Bob Reichert
|
|
|
this is for the concrete encased electrode..Ready after 8:30 this morning. Phone #: ###-#### Inspection requested via web by Bob Glenn ok pour concrete electrode
|
Issue PAID IN FULL permit | | | 7/8/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/8/2016 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|