Final | 11/11/2016 | 11/14/2016 | 11/14/2016 | P | PASS |
Rock A. Hudson
|
|
|
Call Mitch 30 minutes prior. Phone #: ###-#### Inspection requested via web by Mitch Whited Final ok
|
Final | 9/29/2016 | 9/30/2016 | 9/30/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Please Mitch 30 minutes prior. Phone #: ###-#### Inspection requested via web by Mitch Whited 210.12- All outlets in bedroom areas shall have AFCI protection. Lighting not protected. 404.8- Circuit directory shall be complete. 406.12- All receptacle outlets installed in basement shall be tamper resistant type. All need replaced.
|
Electrical Rough-In | 7/8/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Eric Story
|
|
|
Call Mitch 30 minutes prior to the inspection. Phone #: ###-#### Inspection requested via web by Mitch Whited whole basement remodel ok cover
|
Issue PAID IN FULL permit | | | 7/8/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/8/2016 | | DONE |
|
|
|
This permit was created on the web by Mitch Whited
|