First Notice | 7/29/2016 | 7/29/2016 | 8/7/2016 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Jay Symonds
|
Final | 7/28/2016 | 7/29/2016 | 7/29/2016 | A | PASS |
Eric Story
|
|
|
The code to lock box is 2323 Phone #: ###-#### Inspection requested via web by Jay Symonds corrections fixed final ok
|
Final | 7/28/2016 | 7/28/2016 | 7/28/2016 | P | FAIL |
Bob Reichert
|
|
|
Code if not open is 2323 to lock box Phone #: ###-#### Inspection requested via web by Jay Symonds called, left correction notice, NEC 408.4 (A) shall provide circuit directory for each panel shall be clear, concise, and evident, specific purpose shall be described, 210.8 (B) (1), (5) shall provide gfci protection for 3 bathroom receptacles and 1 within 6' of sink
|
Electrical Rough-In | 7/14/2016 | 7/14/2016 | 7/14/2016 | P | PASS |
Rock A. Hudson
|
|
|
lock box code 2323 Phone #: ###-#### Inspection requested via web by Jay Symonds Walls and ceilings rough in ok cover
|
Electrical Rough-In | 7/12/2016 | 7/12/2016 | 7/12/2016 | A | FAIL |
Rock A. Hudson
|
|
|
lock box is on hand rail code is 2323 Phone #: ###-#### Inspection requested via web by Jay Symonds 517.13- All receptacles located in patient care areas shall have metallic raceway installed as identified in 250.118. Alluminum flex shall not be installed in lengths exceeding 6' for effective fault path.
|
Issue PAID IN FULL permit | | | 7/12/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/12/2016 | | DONE |
|
|
|
This permit was created on the web by Jay Symonds
|