Final | 9/2/2016 | 9/2/2016 | 9/2/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Corrections fixed final ok
|
Final | 9/2/2016 | 9/2/2016 | 9/2/2016 | A | NR |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov not ready
|
Final | 9/1/2016 | 9/1/2016 | 9/1/2016 | P | FAIL |
Eric Story
|
|
|
Garage door will be unlocked out back Phone #: ###-#### Inspection requested via web by daniel bibikov 406.5 receptacles shall be securely mounted(washer and other recept in laundry in-op) 110.3(b) shall not exceed manufactors specifications (main for sub-panel is in a max load 50 amp location in main) 422.30 Disconnect required for dishwasher&furnace
|
Rough-In Permanent Service | 8/2/2016 | 8/3/2016 | 8/3/2016 | A | PASS |
Eric Story
|
|
|
New garage and service Phone #: ###-#### Inspection requested via web by daniel bibikov plumbing&hvac companies did not have permits,need to get with daniel it is obvious electrical work was done without inspections being called in,boxes used were rough-in style not remodel style. Garage only ok-cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 7/20/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/20/2016 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|