Final | 8/24/2016 | 8/24/2016 | 8/24/2016 | P | PASS |
James Ady
|
|
|
reinspection please Phone #: ###-#### Inspection requested via web by Celinda Winters final ok
|
Final | 8/23/2016 | 8/24/2016 | 8/24/2016 | A | FAIL |
Rock A. Hudson
|
|
|
The back door will be open for entrance Phone #: ###-#### Inspection requested via web by Celinda Winters 210.8- Kitchen GFCI device to left of sink not working. Shows not power and will not reset.
|
Electrical Rough-In | 8/2/2016 | 8/2/2016 | 8/2/2016 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters corrections made, ri ok kitchen, baths
|
Electrical Rough-In | 8/1/2016 | 8/2/2016 | 8/2/2016 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Winters called, left correction notice, NEC 300.4(A) shall provide nailplate if edge of bored hole less than 1 1/4" from face od framing member, 334.15 shall protect nm cable under kitchen counter, 334.30 shall secure nm within 12" of box, 110.12(A) shall close unused openings
|
Issue PAID IN FULL permit | | | 7/20/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/20/2016 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|